Configuration software KS2000
Step Down and off
Sets the current lamp power value one step lower without fading (sends DALI command 7 [} 53]
lamp is already set to its parameterized minimum (MIN) value, it is switched off. The MIN value can be
parameterized on the Variables [} 31] tab.
On and Step Up
Sets the current lamp power value one step higher without fading (DALI command 8 [} 53]
switched off, it is switched on and is set to its parameterized minimum (MIN) value. The MIN value can be
parameterized on the Variables [} 31] tab.
Recall MIN LEVEL
Sets the lamp power value to the parameterized minimum (sends DALI command 6 [} 53]
was switched off, it is switched on.
Recall MAX LEVEL
Sets the lamp power value to the parameterized maximum (sends DALI command 5 [} 53]
was switched off, it is switched on.
Go to Scene
• Select a scene.
• Click the Go to scene button.
Sets the DALI device's lamp power value to the level parameterized for the selected scene (sends a DALI
command between 16 and 31 [} 53]
Queries
This dialog allows you to inquire about information regarding the status of the DALI device:
• Select the desired query.
• Click the Send query button.
Query ballast
Asks whether the DALI device is ready for data exchange (DALI command 145 [} 55]dec).
Query lamp failure
Asks whether the DALI device has a lamp problem (DALI command 146 [} 55]
Query lamp power supply switched on
Asks whether the power supply to the DALI device has been switched on (DALI command 147 [} 55]
Query limit value error
Asks whether a limit value error has occurred on the DALI device (DALI command 148 [} 55]
Query reset status
Asks whether the DALI device is in the reset state (DALI command 149 [} 55]
Query missing short address
Asks whether the DALI device is missing the short address (DALI command 150 [} 55]