Beckhoff KL6811 Documentation page 33

Dali/dsi master terminal with integrated power supply
Table of Contents

Advertisement

The following values result:
n
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Direct address
This variable contains the DALI device's short address. A valid short address lies in the range between 0
and 63
. If 255
is written into the variable, the short address is deleted.
dec
dec
Status information
This variable can only be read. It contains the DALI device's status byte. The bits in the status byte have the
following significance:
Bit Name
7
Power supply fault
6
Missing short address
5
Reset status
4
Fading done
3
Limit value error
2
Lamp power
1
Lamp failure
0
Status of the DALI device
Version number
Displays the DALI device's version number. This variable is entered by the device manufacturer, and can
only be read!
Physical minimum level
Indicates the lowest physically possible lamp power that the DALI device can adopt. This variable is entered
by the device manufacturer, and can only be read!
KL6811
absolute fade time
< 0.707 s
0.707 s
1.000 s
1.414 s
2.000 s
2.828 s
4.000 s
5.657 s
8.000 s
11.314 s
16.000 s
22.627 s
32.000 s
45.255 s
64.000 s
90.510 s
Meaning
0
No
bin
0
No
bin
0
No
bin
0
Fading has been completed
bin
1
Fading in progress
bin
0
The most recently requested lamp power value was between the MIN
bin
and MAX values, or was OFF.
0
OFF
bin
1
ON
bin
0
OK
bin
0
OK
bin
Version: 2.0.0