Alpha ESS Storion-T50 Installation Manual page 41

Energy storage system
Hide thumbs Also See for Storion-T50:
Table of Contents

Advertisement

PCS and PE are respectively connected to A(L1)/B(L2)/C(L3) phases of generator AC
output and PE.
F.
Confirm wiring firmness.
Rated power
50kW
100kW
Take a multimeter to make sure that there is no dangerous voltage (voltage<36V)
at connection points during wiring.
All wires are connected to the wiring terminals externally from the wiring holes at
the bottom of PCS. After wiring, fireproofing mud should be used to seal the
wiring holes.
Please refer to the following diagram to connect power cables.
Figure 4-23 AC-Side wiring diagram, off-grid mode
______________________________________________________________________
Installation
Table 21 AC cable description
Copper AC line section recommendation (mm²)
≥25(Load port); ≥50(Grid port);
≥50(Load port); ≥95(Grid port);
Alpha ESS Co., Ltd.
Your Smart Energy
Page 39 of 48

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Storion-t100

Table of Contents