7. Programming the full range of functions (FULL)

7.1 Event input (EIFN)

The connection of the event input is done as described
in chapter 5.10. There are three different possibilities for
control.
1. potential-free switch or relay
2. open collector on continuity
3. TTL Logic voltage
There are 10 program functions available for the event
input:
NONE : The event input is deactivated. The controller
uses PB1, TI1 and TD1 for PID control and SP1
(if not changed via other parameters) as set
point.
SP2
: SP2 replaces SP1 when EIFN is activated
PID2 : PB2, TI2, TD2 replace when activating the EIFN,
PB1, TI1, TD1
SPP2 : SP2, PB2, TI2, TD2 replace when activating the
EIFN, SP1, PB1, TI1, TD1
RSA1 : The EIFN resets the alarm output 1.
RSA2 : The EIFN resets the alarm output 2.
RA12 : The EIFN resets the alarm output 1 and 2.
DO1 : The EIFN deactivates output 1 (OUT1, MV1=0).
DO2 : The EIFN deactivates output 2 (OUT2, MV2=0).
DO12 : DO1 : The EIFN deactivates output 1 and 2 (MV1=0 & MV2=0).
LOCK : All parameters are locked.
SP2F Funktion: With the function SP2F you can define whether SP2 replaces SP1
(setting AC-TU) or whether SP2 is added to SP1 (setting DEVI).
SP2F = ACTU SP2 replaces SP1
SP2F = DEVI Set point = SP1 + SP2
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
connections:
E-Mail: office@promesstec.com I Internet: www.promesstec.com
Event input +
Event input -
72