promesstec UREG 200 User Manual page 64

Universal controller
Table of Contents

Advertisement

Warm start Automatic setting
The difference between hot and cold start is that the warm-up phase is omitted in the
case of a hot start, since the process is already at the target level.
Automatic setting error
If the automatic setting fails, the error message ATER appears in the
upper display together with:
- When PB exceeds 9000 (9000 PU, 900,0 °F or 500,0 °C)
- Or TI exceeds 1000sec.
- Or the setpoint has been adjusted during the setting cycle
- Or the event input was switched.
Troubleshooting for errors
- Start the automatic setting again
- Do not change the set point during the setting cycle
- Do not switch the event input during the setting cycle
- Use the manual setting (see chapter 6.19)
- Press a key to delete the message