promesstec UREG 200 User Manual page 21

Universal controller
Table of Contents

Advertisement

Included
Base
Parameter
in
function
Name
Yes
A1FT
Yes
A2FN
Yes
A2MD
Yes
A2FT
No
EIFN
No
PVMD
s
etup
Menu
No
FILT
yes
SELF
Yes
SLEP
No
SPMD
Yes
SP1L
Yes
SP1H
No
SP2F
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
Parameter
Display
describtion
Alarm 1 Error behavior
Alarm 2 function
Alarm 2 mode
Alarm 2 Error behavior
Event input function
PV Mode selection
Damping filter for PV
Self-optimization
Sleep mode
Set point mode
SP1 LOW-Value
SP1 HIGH-Value
Setpoint 2 format
Range
0
: Alarm output OFF in case of error
1
: Alarm output ON in case of error
See alarm 1 function
See alarm 1 mode
See alarm 1 Error behavior
0
: No event function
1
: SP2 replaces SP1
2
: PB2, TI2, TD2 replaces PB1, TI1, TD1
3
: SP2, PB2, TI2, TD2 replaces SP1, PB1,
TI1, TD1
4
: Reset alarm output 1
5
: Reset alarm output 2
6
: Reset alarm 1 & 2
7
: Output 1 deactivate
8
: Output 2 deactivate
9
: Output 1 & 2 deactivate
10
: Lock all parameters
0
: PV1 as process value
1
: PV2 as process value
2
: PV1 - 2 as process value
3
: PV2 - 1 as process value
0
: 0 Seconds
1
: 0,2 Seconds
2
: 0,5 Seconds
3
: 1 Seconds
4
: 2 Seconds
5
: 5 Seconds
6
: 10 Seconds
7
: 20 Seconds
8
: 30 Seconds
9
: 60 Seconds
0
: deactivate
1
: activate
0
: deactivate
1
: activate
0
: SP1 or SP2 as setpoint ( depending
on EIFN-setting
1
: Minute ramp as setpoint
2
: Hour ramp as setpoint
3
: IN1 as set point
4
: IN2 as set point
5
: Selection for pump control
Low: -19999 High: 45536
Low: -19999 High: 45536
0
: SP2 is a direct value
1
: SP2 is a difference value
E-Mail: office@promesstec.com I Internet: www.promesstec.com
Standard
Value
1
2
0
1
1
0
2
0
0
0
0 °C
1000 °C
0
21

Advertisement

Table of Contents
loading

Table of Contents