Output 1 And 2 (Out1 / Out2) - promesstec UREG 200 User Manual

Universal controller
Table of Contents

Advertisement

Example IN1L and IN1H settings:
If a 4-20mA sensor is selected as IN1, the sensor LOW value (SL) is 4mA, the sensor
HIGH value (SH) is 20mA. The input signal looks like this:
Input for linear sensors
Process value
����1 = ����1�� + ( ����1�� − ����1�� ) ∗
Formula:
Example:
Pressure transmitter with the range of 0 - 15 bar is connected to input 1,
with 4-20mA
Output signal connected. Please make the following settings:
IN1 = 4 - 20 IN1L = 0.0
IN1U = PU
DP1 = 1-DP
To change the resolution, you can also make other settings at DP1.

6.2 output 1 and 2 (OUT1 / OUT2)

O1TY: Select the output signal for output 1 (OUT1)
The selection must match the installed module (see type code)
Possible output signals are:
RELY: Switching output relay (type –A)
SSRD: Pulsed voltage output as SSR driver (type -C)
SSR: Switching output for controlling SSR relays (in planning)
4 - 20: 4 - 20 mA Current output (type –B)
0 - 20: 0 - 20 mA Current output (type –B)
0 - 1 V: 0 - 1 V Voltage output (in planning)
0 - 5 V: 0 - 5 V Voltage output (in planning)
1 - 5 V: 1 - 5 V Voltage output (in planning)
0 - 10V: 0 - 10 V Voltage output (in planning)
O2TY: Select the output signal for output 2 (OUT2)
The selection must match the installed module (see type code)
Same selection options as output 1 (O1TY).
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
Input signal
IN1H = 15.0
E-Mail: office@promesstec.com I Internet: www.promesstec.com
��−����
����−��
44

Advertisement

Table of Contents
loading

Table of Contents