Chapter 5
Configure the Configurable Flowmeter Module
Configuring CFM Modules in
a Remote Chassis
86
ControlLogix ControlNet® interface modules (1756-CNB or 1756-CNBR) are
required to communicate with 1756-CFM modules in a remote chassis.
You must configure the communications module in the local chassis and the
remote chassis before adding new I/O modules to the program.
1. Create a 1756-CNB or 1756-CNBR module in the local chassis.
1. Select I/O Configuration.
2. Click the right mouse button to
display the menu.
3. Select New Module
2. Choose a 1756-CNB or 1756-CNBR module on the Select Module Type
screen.
3. Configure the 1756-CNB or 1756-CNBR module.
For more information on the ControlLogix ControlNet Interface
modules, see the ControlLogix ControlNet Interface User Manual,
publication CNET-UM001.
4. Create a 1756-CNB or 1756-CNBR module for the remote chassis.
Select the local communications module.
Click the right mouse button and select New Module.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Notice that the remote 1756-CNB
module is added to the Controller
Organizer through the local 1756-
CNB module.