Connect Ungrounded End Of The Cable; Connect Wires To The Rtbs - Allen-Bradley 1756-CFM User Manual

Controllogix configurable flowmeter module
Table of Contents

Advertisement

Chapter 4
Install the Configurable Flowmeter Module
60

Connect Ungrounded End of the Cable

1. Cut the foil shield and drain wire back to the cable casing and apply
shrink wrap.
2. Connect the insulated wires to the RTB as shown in the next section.

Connect Wires to the RTBs

There are two types of RTBs available for use with the 1756-CFM module:
1756-TBSH Spring Clamp RTB
1756-TBNH NEMA Screw RTB
1756-TBSH Spring Clamp RTB
1. Strip 11mm (7/16 in.) maximum length of wire.
2. Insert the screwdriver into the inner hole of the RTB, as shown in this
figure.
3. Insert the wire into the open terminal and remove the screwdriver.
1756-TBNH NEMA Screw RTB
1. Strip 8mm (5/16 in.) maximum length of wire.
2. Turn the terminal screw counterclockwise.
3. Wrap wire around the terminal.
4. Turn the terminal screw clockwise until it tightens on the wire.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021