Changing Configuration During Cfm Module Operation; Using Ladder Logic - Allen-Bradley 1756-CFM User Manual

Controllogix configurable flowmeter module
Table of Contents

Advertisement

Chapter 5
Configure the Configurable Flowmeter Module
Changing Configuration
During CFM Module
Operation
80
After the module has begun operation, you can only change configuration by
using ladder logic and message instructions.
Follow these steps to change module configuration during operation:
1. Access the data structures through the tag monitor to make specific
configuration changes, see
2. Use ladder logic and a configuration message instruction to send the
configuration changes to the module, see below through

Using Ladder Logic

You must use ladder logic to perform these operations on your module:
change configuration
perform run time services
Ladder logic uses message instructions to exchange data between the
controller and module. You can access the ladder logic by double-clicking on
the Main Routine portion of the MainProgram.
Double-click here to enter
the Main Routine
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
page
77.
page
85.