Operating in Totalizer Mode

In Totalizer mode, the 1756-CFM module counts pulses and scales them to
engineering units. Every effort is made to store the least significant count even
when the least significant unit of the total is larger. The module calculates
three forms of calculated frequency:
Frequency over a fixed period
Frequency over a requested number of samples
Moving average of the frequency
All of the forms mentioned above are available in Totalizer mode. In this mode,
the module also offers these functions:
Prover function
Filler function
These functions are described later in this chapter.

Nonresettable Totalizer

Configure the module for Nonresettable Totalizer mode to make sure the total
counts value is not reset during normal module operation. The module stores
total count values up to 2
The total count value can be reset in Nonresettable Totalizer mode if
IMPORTANT
power is cycled to the module for any reason (for example, module is
removed from and reinserted to the chassis).

Terminal Usage in Totalizer Mode

In Totalizer mode, F0 and F1 are used as inputs. Z0 and Z1 are used as prover
signals.

Output Operation in Totalizer Mode

In Totalizer mode, outputs:
can operate normally or be forced ON or OFF.
can be tied to either flowmeter input. If one channel is configured for
trickle operation, both outputs are tied to that flowmeter input.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 3
Configurable Flowmeter Module Features and Operational Modes
31
-1 (2,147,483,647) counts.