Enter Message Configuration - Allen-Bradley 1756-CFM User Manual

Controllogix configurable flowmeter module
Table of Contents

Advertisement

Chapter 5
Configure the Configurable Flowmeter Module
Click here to see the message
configuration pop-up screens
Message Type is CIP Generic
Service Code is 4c
Class Name is 4
Instance Name is 16
84

Enter Message Configuration

After creating a new tag, you must enter message configuration.
Enter message configuration on these screens:
Configuration Pop-up Screen
Communications Pop-up Screen
Tag Pop-up Screen
A description of the purpose and setup of each screen follows.
Configuration Pop-up Screen
This screen provides information on what module service to perform and
where to perform it.
For example, the screen below shows the information needed to send a
configuration message (module service) to a 1756-CFM module (where to
perform service).
This table contains information that must be entered on the configuration
screen to perform the example flowmeter module service:
Field
Service Code
Class Name
Instance Name
Source
Number of Elements
Destination
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Select
4c
4
16
Local:1:C (dependent on module location)
300
N/A
Source is Local:1:C
Num. Of Elements is
300

Advertisement

Table of Contents
loading

Table of Contents