Alarms With The Filler Function; Sample Configuration For Totalizer Mode Filler Function - Allen-Bradley 1756-CFM User Manual

Controllogix configurable flowmeter module
Table of Contents

Advertisement

Fill Transition
Fill Transition is the user-defined Net Volume value to switch from full flow to
trickle flow.
Fill Transition Timer
After the transition from full flow to trickle flow, the Fill Transition Timer
value determines how long the trickle will last (that is, this feature sets the time
that the trickle valve is open or ON).

Alarms with the Filler Function

The module offers these alarms when operating the filler function:
Overflow Alarm - TotalCounts > RollOver Value
Overrange Alarm - FreqPeriod > 100kHz
Overspeed Alarm - Speed > Highest Allowed Frequency
Acceleration Alarm - Acceleration > Acceleration Alarm Value
You must enable each alarm. When any of the alarms occur, it is latched and
remains on until you reset the alarm. (Toggle the alarm enable bit to reset the
alarm.)

Sample Configuration for Totalizer Mode Filler Function

To see a sample configuration for a 1756-CFM module using Totalizer mode
filler function, including the use of all the features mentioned in the previous
section, see
page
96.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 3
Configurable Flowmeter Module Features and Operational Modes
51