Trickle Function for Totalizer Mode

The trickle function is used with the filler function to improve volume
repeatability in a filling application. The trickle function requires two filling
lines and an optional discrete module to activate the trickle valve. Activation of
the valve should be sized for worst case volume at least 100 ms based on typical
program scan = 5 ms and an output module RPI = 25 ms.
For most of the filling process, the full flow state is assigned to one of the
module's outputs. For more repeatable fills or to prevent overfills, the
pretrigger feature helps make sure that the full flow valve turns off before it
reaches the
Fill Transition
When the filling application reaches the user-defined
trickle Totalizer mode changes the application from the full flow line to the
trickle flow line. This slower line allows the application to finish the filling
process without any waste.
For more information on the
The filler function can be used in any of these conditions:
Starting with the trickle flow
Filling with the full flow only
Restarting the timed trickle flow
Starting the trickle flow prior to the fill transition
Restarting full flow while in trickle flow
Using the Trickle feature in previously mentioned conditions requires specific
configuration changes.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 3
Configurable Flowmeter Module Features and Operational Modes
or
Fill Total Target
volume.
Fill Transition
feature, see
Fill Transition
point, the
page
51.
45