Environmental Conditions - Siemens SINAMICS PERFECT HARMONY GH150 6SL3826 Operating Instructions Manual

Medium-voltage drive
Table of Contents

Advertisement

Technical data and drawings
B.2 Environmental conditions
B.2

Environmental conditions

Climatic environmental conditions
Table B-2
Climatic environmental conditions
Ambient temperature
Relative humidity
Other climatic conditions ac‐
cording to class
Pollution degree
Mechanical ambient conditions
Table B-3
Mechanical ambient conditions
Class
126
Storage with suitable packag‐
ing
-25° C to +70° C
5% to 95%
(Only low condensation is
permitted. The device must
be completely dry before
commissioning.)
1K22 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
Icing not permissible
2 without conductive pollution
according to DIN EN 50178 /
VDE 0160
(IEC 62103)
Storage with suitable packag‐
ing
1M11 according to
DIN EN 60721‑3‑1
(IEC 60721‑3‑1)
Transport with suitable pack‐
aging
-25° C to +70° C
5 % to 95 %
(Only slight condensation is
permissible. The device must
be completely dry before
commissioning.)
2K11 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
2 without conductive pollution
according to DIN EN 50178 /
VDE 0160
(IEC 62103)
Transport with suitable pack‐
aging
2M4 according to
DIN EN 60721‑3‑2
(IEC 60721‑3‑2)
SINAMICS PERFECT HARMONY GH150 6SL3826
Operation (industrial)
5 °C to +50 °C
5 % to 95 %
(condensation is not permit‐
ted)
3K3 according to DIN EN
60721‑3‑3/A2:1997
(IEC 60721‑3‑3/Ed2.2:2008)
2 without conductive pollution
according to DIN EN 50178 /
VDE 0160
(IEC 62103)
Operation
3M1 according to
DIN EN 60721‑3‑3/A2:1997
(IEC 60721‑3‑3/Ed2.2:2008)
Operating Instructions 05/2020