The RUGGEDCOM RP110 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
61000-4-2
61000-4-3
61000-4-4
61000-4-5
61000-4-6
61000-4-8
61000-4-29
61000-4-11
61000-4-12
61000-4-16
28
Test
IEC
ESD
IEC
Radiated RFI
IEC
Burst (Fast Transient)
IEC
Surge
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
Description
Enclosure
Contact
Enclosure Air
Enclosure
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
a
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
a
± 4 kV Line-to-Earth
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
1000 A/m Continuous for
1 s, 100 A/m for 3 min
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
30% for 1 period,
60% for 50 periods
100% for 5 periods,
100% for 50 periods
a
1 kV Common
2.5 kV Common, 1 kV
Differential Mode @ 1 MHz
2.5 kV Common, 1 kV
Differential Mode @ 1 MHz
30 V Continuous,
300 V for 1 s
30 V Continuous,
300 V for 1 s
Installation Manual, 01/2021, C79000-G8976-1012-04
Severity
Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
 
 
 
 
2
3
3
4
4
RUGGEDCOM RP110