Connecting Power; Connecting High Ac/Dc Power - Siemens RUGGEDCOM RP110 Installation Manual

Hide thumbs Also See for RUGGEDCOM RP110:
Table of Contents

Advertisement

1
1
2
3
Figure 2.3
2.6

Connecting Power

The RUGGEDCOM RP110 supports a single high AC or low DC power supply.
The RUGGEDCOM RP110 is equipped with a screw-type terminal block, which
provides power to the AC/DC power supply.
Note
2.6.1

Connecting High AC/DC Power

To connect a high AC/DC power supply to the device, do the following:
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a DC power supply terminal block. Damage to
the power supply may occur.
RUGGEDCOM RP110
Installation Manual, 01/2021, C79000-G8976-1012-04
Chassis Ground Connection
#6-32 Screw
#6 Ring Lug
Chassis Ground Connection
For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
For 125-250 VDC rated equipment, an appropriately rated DC circuit breaker
must be installed.
Use minimum #16 gage copper wiring when connecting terminal blocks.
A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
It is recommended to provide a separate circuit breaker for each power supply
module.
Equipment must be installed according to applicable local wiring codes and
standards.
NOTICE
Installing the Device
2.6 Connecting Power
2
3
9

Advertisement

Table of Contents
loading

Table of Contents