Section 3: PRO2000V4_RED Implementation

The card consists in a double PCB that is installed inside the actuator housing. It is connected to the
ICON3000 actuators base card via strip connector. The internal wiring connects the PROFIBUS data
lines to the actuator terminal board.
3.1

Communication Features

Communication protocol
Network topology
Transmission medium
Data rate
Cable length without repeater
Station type
Device number
Bus access
Electrical power
Bus termination
Temperature
Fieldbus redundancy
EMC protections
Types of operation
Baud rate
Addressing
PRO2000V4_RED Implementation
Section 3: PRO2000V4_RED Implementation
: PROFIBUS DP according to EN 50170
: Line (bus) structure. With repeaters tree structures
can also be realized
: Twisted, screened copper cable according to EN 50170
: 9.6
19.2
45.45 93.75
: 1,200 1,200 1,200 1,200
: DPV1 and DPV2 (redundancy) slave
: 32 devices per segment without repeater
(max 126, with repeaters)
: Token-passing between masters and polling for slaves
: Actuator powered (as option: auxiliary external voltage supply)
: Configurable on board via local operator interface of actuator
: -40 °C, +85 °C
: Two independent communication interfaces
: EN 50081-2 and EN 50082-2
: Cyclic data exchange, Sync mode, Freeze mode, Fail safe mode
: Automatic recognition
: Configurable via local operator interface
April 2021
187.5
500
1500 Kbit/second
1,000
400
200
m
3