Master Controller (PLC) Commissioning
Timer Close Direction – Status
It enables the Timer function in Close direction.
Value:
0: Off - disable (default setting)
1: On
Timer Close Direction – On time
It defines the On time of the Timer function in closing.
Value:
minimum
2 seconds
maximum
200 seconds
default value: 2 seconds
Timer Close Direction – Off time
It defines the Off time of the Timer function in closing.
Value:
minimum
1 second
maximum
200 seconds
default value: 2 seconds
Timer Close Direction – Start position
It defines the start position of the Timer function in closing.
Value:
minimum
100%
maximum
0%
default value: 100%
Timer Close Direction – Stop position
It defines the stop position of the Timer function in closing.
Value:
minimum
0%
maximum
100%
default value: 0%
Reserved
Dead band
It defines in tenth of % the Dead band of the positioning function available on the
modulating actuator. The movement is inhibited until the difference between current
position and requested position (position error) is lower than Dead band.
Value:
minimum
1
maximum
255
default value: 10
Motion inhibit time
It defines the minimum delay between two cycles of the motor when the actuator is in
modulating service. It allows to adjust the number of start per hour of the electric motor.
Value:
minimum
1 second
maximum
255 seconds
default value: 6 seconds
Section 8: Master Controller (PLC) Commissioning