General Introduction; Operating Conditions; Delivery And Storage; Delivery - Grundfos Hydro EN Installation And Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

be also provided:
• Diesel engine installation and operating instruction manual;
• Batteries safety data sheet;
• Factory test report for diesel driven pump as required by the
EN 12845.
2.

General introduction

The automatic Hydro EN pumping set for automatic sprinkler
system are made in compliance with the requirements of the
following standards of reference:
• EN 12845 - Automatic fire sprinkler systems
• UNI 10779 - Hydrant networks
• UNI 11292 - Compartments for installation of fire fighting
pumping sets (for the applicable aspects).
The Hydro EN pumping set are designed for automatic sprin-
kler system such single, superior single, double or combined
water supply sources.
According to the norm prescriptions, in the pumping sets with
two pumps, each pump installed must be able to supply the
design performance; in the three pump pumping sets instead,
each must deliver 50% of the flow rate at the required design
head.
For diesel driven pumps, a functional factory test with perfor-
mance testing is performed; the all test data are recorded on a
bulletin.
The main pumps are subjected to automatic start and manual
stop.
The automatic stop function, for hose reels systems only (UNI
10779) is always included and and can be activated, if neces-
sary, by following the procedures outlined in the dedicated
paragraphs.
3.

Operating conditions

Installation:
indoor, protected from the weather.
Installation height:
up to 300 m.a.s.l.
Performances:
see specific performance curve for
the chosen model, performance
according to ISO 9906.
Nominal pressure:
components and materials PN16.
Pumped liquid:
solid and fibre free fresh water.
Water temperature:
from 0 °C to +50 °C.
Ambient temperature:
from +4 °C to +40 °C
(min.+10°C for diesel driven
pumps).
Suction lift:
according to specific performance
of the model chosen.
Max. inlet pressure:
is related to the maximum pressure
delivered by the pump; the sum
of the inlet pressure with the max.
pressure delivered by the pump
must be less than the maximum
operating pressure.
Electric power
according to the specific chosen
installed:
model.
Starting:
Direct-on-line (DL) up to 30 kW.
Star/delta from (SD) 37 kW.
Main supply:
for electirc pumps 3x400V, 50Hz,
3P+PE
for diesel pumps 1x230V, 50Hz,
1P+N+PE, Imax=4A.
4.

Delivery and storage

4.1

Delivery

To facilitate handling, pumping units are shipped from the
factory in macro blocks designed for the transport of forklift or
similar device.
Use appropriate tools and devices, in compliance with the
safety requirements.
Lift the pump set by means of the lifting eyes
of the base frame. Never use the lifting eyes
of the individual components. The lifting point
should always be above the centre of gravity of
the pump set. Alternatively, a forklift truck can
be used.
Use only lifting equipment in proper condition.
Lock the cabinet door before moving the pump-
ing set.
Electric unit.
Diesel unit.
See also installation and operating instructions for the diesel.
engine.
4.2

Storage

The pump set must be stored in a frost-free
Caution
room.
In order to prevent water, dust, etc. from entering the pump, all
openings must be covered until pipes are connected.
See also installation and operating instructions for the diesel
engine.
5