6.2 EMC and Environmental Type Tests
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX1400 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
Burst (Fast Transient)
IEC 61000-4-5
IEC 61000-4-6
Induced (Conducted) RFI
IEC 61000-4-8
IEC 61000-4-9
Pulse Magnetic Field
IEC 61000-4-11
Voltage Dips & Interrupts
IEC 61000-4-16
Mains Frequency Voltage
IEC 61000-4-17
60
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
Description
ESD
Radiated RFI
Surge Immunity
Magnetic Field
Ripple on DC
Power Supply
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
Enclosure Ports
AC Power Ports
Signal Ports
DC Power Ports
DC Power Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
± 2 kV Line-to-Earth
± 1 kV Line-to-Line
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
10 V
100 A/m Continuous
1000 A/m for 1 s
300 A/m
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
30 V Continuous
300 V for 1s
10%
Installation Manual, 01/2021, C79000-G8976-1103-17
Severity
Levels
4
a
Note
4
 
3
4
3
5
4
 
4
3
RUGGEDCOM RX1400