Certification
Agency
FDA/CDRH
ISO
Section 6.3

EMC and Environmental Type Tests

The RUGGEDCOM RSG2100 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
NOTE
• In the case of an all fiber port configuration, this product meets all Class 2 requirements. Otherwise,
all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during which disturbance
errors may occur but recovery is automatic.
• If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during which no disturbance
errors will occur.
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
42
21 CFR Chapter I, Sub-chapter J
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Standards
ISO9001:2008
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
+/- 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
+/- 4 kV Line-to-Ground,
+/- 2 kV Line-to-Line
DC Power Ports
+/- 2 kV Line-to-Ground,
+/- 1 kV Line-to-Line
AC Power Ports
+/- 4 kV Line-to-Ground,
+/- 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
40 A/m, continuous,
Comments
Approved
Designed and manufactured using an
ISO9001:2008 certified quality program
Test Levels
Severity Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV
10 V
1000 A/m for 1 s
EMC and Environmental Type Tests
RUGGEDCOM RSG2100
Installation Guide
4
a
Note
a
Note
4
4
3
4
3
a
Note