Buzzer Duration (B1); Alarm Delay (Ad); Activity Frequency (Af) - Elstat ems75sz Manual

Hide thumbs Also See for ems75sz:
Table of Contents

Advertisement

9.29

Buzzer duration (b1)

The table below details the buzzer duration (b1) parameter.
Display
Defines the duration of the buzzer for door open alarm conditions.
Description
If the door remains open after the buzzer duration (b1), the EMS controller
switches off the compressor.
The EMS controller switches off the compressor after the duration defined
Considerations
by alarm delay (Ad) + buzzer duration (b1 ).
Not used on ems55advanced and ems55Radvanced OFC firmware
Range
1 to 254 seconds
Global default
60 seconds
9.30

Alarm delay (Ad)

The table below details the alarm delay (Ad) parameter.
Display
Defines the maximum time the cooler door can be open before sounding the
Description
alarm buzzer.
If disabled, the door switch is also disabled.
The EMS controller does not detect door openings, therefore, the EMS con-
troller does not:
Considerations
Range
00 to 30 minutes
Global default
00 (disabled)
9.31

Activity frequency (AF)

The table below details the activity frequency (AF) parameter.
Display
Defines the minimum number of door openings or motion counts to indicate
Description
an active 30 minute period in the self-learning matrix, as described below.
Considerations
See below.
Range
See below
Global default
00 (low frequency)
update the self-learning matrix for door activity.
l
manage the evaporator fan management for door activity.
l
sound door alarms if the door is left open.
l
76 of 86
27 February 2014