Standard Specifications - Mitsubishi Electric -MR-CV User Manual

Power regeneration converter unit
Table of Contents

Advertisement

1.3

Standard specifications

200 V class
Model MR-CV_
Output
Rated voltage
Rated current [A]
Main circuit power
Voltage/Frequency
supply input
Rated current [A]
Permissible voltage fluctuation
Permissible frequency fluctuation
Power supply capacity [kVA]
Inrush current [A]
Control circuit power
Voltage/Frequency
supply input
Rated current [A]
Permissible voltage fluctuation
Permissible frequency fluctuation
Power consumption [W]
Inrush current [A]
Interface power
Voltage
supply
Current capacity [A]
Capacity [kW]
Protective functions
Main circuit method
Continuous rating [kW]
Instantaneous maximum rating [kW]
Satisfied standards
CE marking
UL standard
Structure (IP rating)
Environment
Ambient temperature
Ambient humidity
Ambience
Altitude
Vibration resistance
Mass [kg]
*1 This value is applicable when all I/O signals are used. Reducing the number of I/O points decreases the current capacity.
*2 This does not apply to the terminal block.
*3 Refer to the following for restrictions on using this product at an altitude exceeding 1000 m and up to 2000 m.
Page 15 Restrictions when using this product at an altitude exceeding 1000 m and up to 2000 m
1 FUNCTIONS AND CONFIGURATION
8
1.3 Standard specifications
11K
18K
270 V DC to 324 V DC
41
76
3-phase 200 V AC to 240 V AC, 50 Hz/60 Hz
35
65
3-phase 170 V AC to 264 V AC
Within ±3 %
Page 67 Power supply capacity and generated loss
Page 69 Inrush currents at power-on of main circuit and control circuit
1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz
0.2
1-phase 170 V AC to 264 V AC
Within ±3 %
30
Page 69 Inrush currents at power-on of main circuit and control circuit
24 V DC ±10 %
*1
0.35
11
18
Undervoltage protection, regenerative error protection, regenerative overvoltage shut-off, MC
drive circuit error protection, open-phase detection, inrush current suppression circuit error
protection, main circuit device overheat error protection, cooling fan error protection, overload
shut-off (electronic thermal)
Converter with power regeneration function
7.5
11
39
60
LVD: EN 61800-5-1
EMC: EN 61800-3
MD: EN ISO 13849-1, EN 61800-5-2, EN 62061
UL 508C
Force cooling, open (IP20)
Operation
0 ˚C to 55 ˚C (non-freezing)
Storage
-20 ˚C to 65 ˚C (non-freezing)
Operation
5 %RH to 90 %RH (non-condensing)
Storage
Indoors (no direct sunlight); no corrosive gas, inflammable gas, oil mist or dust
Altitude 2000 m or less
2
5.9 m/s
, 10 Hz to 55 Hz (in each of the X, Y, and Z directions)
6.1
30K
37K
144
164
107
121
30
37
20
22
92
101
*2
*3
12.1
45K
55K
198
238
148
200
45
55
22
37
125
175
25.0