Source I/O Interface; Alarm Output - Mitsubishi Electric -MR-CV User Manual

Power regeneration converter unit
Table of Contents

Advertisement

Source I/O interface

For the MR-CV_ power regeneration converter unit, source type I/O interfaces can be used.
Digital input interface DI
This is an input circuit in which the anode of the photocoupler is the input terminal. Transmit signals from a source (open-
collector) type transistor output, relay switch, etc.
For transistor
TR
Switch
Approx. 5 mA
V
≤ 1.0 V
CES
I
≤ 100 μA
CEO
Digital output interface DO
This is a circuit in which the emitter of the output transistor is the output terminal. When the output transistor is turned on, the
current flows from the output terminal to a load.
A maximum of 2.6 V voltage drop occurs in the converter unit.
MR-CV_
DOCOM
*1 If the voltage drop (a maximum of 2.6 V) interferes with the relay operation, apply high voltage (a maximum of 26.4 V) from an external
source.

Alarm output

When the converter unit is operating normally, the line between B and C is closed. When an alarm occurs, the line between A
and C becomes closed. Connect the converter unit to the alarm output (A/B/C) via a relay coil or by other means.
MR-CV_
*1 For compliance with the IEC/EN/UL/CSA standards, operate at 30 V DC or less.
5 SIGNALS AND WIRING
62
5.7 Interface
MR-CV_
EM1
etc.
Approx. 4.1 kΩ
DICOM
24 V DC
± 10 %
350 mA
If the polarity of the
diode is reversed, the
converter unit will
malfunction.
ALM
Load
etc.
*1
24 V DC
± 10 %
350 mA
Permissible load: 230 V AC 0.3 A, 30 V DC 0.3 A
A
B
C
*1