Connection Of Converter Unit And Servo Amplifier (Mr-J4 Series) - Mitsubishi Electric -MR-CV User Manual

Power regeneration converter unit
Table of Contents

Advertisement

Connection of converter unit and servo amplifier (MR-J4 series)

When introducing a fuse to the DC power supply wiring between the converter unit and the servo amplifier,
use a wire size that takes the protection coordination between the wires and the fuse into consideration.
The following shows the wires used for wiring. Use the wires given in this section or equivalent wires.
Junction
MR-CV_
terminals
L+
L-
DC power lead 1
Wire size
The following table lists selection examples for when 600 V Grade heat-resistant polyvinyl chloride insulated wire (HIV wire) is
used for the DC power supply (L+ and P4, L- and N-) between the converter unit and the servo amplifier.
■200 V class
DC power supply lead 1
Total capacity of servo amplifiers [kW]
1.9 or less
More than 1.9 and up to 3.1
More than 3.1 and up to 5.2
More than 5.2 and up to 8.0
More than 8.0 and up to 11.3
More than 11.3 and up to 15.4
More than 15.4 and up to 20.1
More than 20.1 and up to 26.2
More than 26.2 and up to 27.5
2
*1 The mounting of 50 mm
and 60 mm
area of the conductive parts is equal to or greater than the cross-sectional area shown in this table, or connect one wire each from TE2-
1 or TE2-2.
■400 V class
DC power supply lead 1
Total capacity of servo amplifiers [kW]
4.4 or less
More than 4.4 and up to 6.6
More than 6.6 and up to 9.9
More than 9.9 and up to 15.2
More than 15.2 and up to 22.1
More than 22.1 and up to 27.5
DC power
lead 2
Servo amplifier 1
P4
N-
DC power supply lead 2
Servo amplifier capacity
100 W/200 W/400 W/600 W/750 W/1 kW
2 kW
3.5 kW/5 kW
7 kW
11 kW
15 kW
22 kW
2
wires to L+/L- of the converter unit is not possible. Connect two wires whose total cross-sectional
DC power supply lead 2
Servo amplifier capacity
600 W/1 kW/2 kW/3.5 kW
5 kW
7 kW
11 kW/15 kW
22 kW
Servo amplifier 2
DC power lead 2
P4
N-
DC power lead 1
Wire [mm
2 (AWG 14)
3.5 (AWG 12)
5.5 (AWG 10)
8 (AWG 8)
14 (AWG 6)
22 (AWG 4)
38 (AWG 2)
50 (AWG 1/0)
60 (AWG 2/0)
Wire [mm
2 (AWG 14)
3.5 (AWG 12)
5.5 (AWG 10)
8 (AWG 8)
14 (AWG 6)
22 (AWG 4)
10 OPTIONS AND PERIPHERAL EQUIPMENT
10.2 Selection example of wires
To the next servo amplifier
2
]
*1
*1
2
]
10
91