■Drive unit or servo amplifier
When an alarm occurs on the drive unit or servo amplifier, the status becomes servo-off, but the main circuit power supply is
not shut off, so shut off the main circuit power supply using an external sequence. Input the emergency stop signal of the
controller to the operating drive units or servo amplifiers to change all axes to servo-off. After canceling the alarm on the drive
units or servo amplifiers, the operation is enabled again by turning on the error reset command from the controller.
Converter unit control circuit
power supply
Main circuit power supply
Converter unit alarm
Drive unit (axis the protection
coordination cable is connected)
Control circuit power supply
Drive unit (axis the protection
coordination cable is connected)
Base circuit
Servo-on command
(From the controller)
Drive unit (axis the protection
coordination cable is connected)
Alarm
Reset command
(From the controller)
Drive unit (axis the protection
coordination cable is not
connected) or servo amplifier
Control circuit power supply
Drive unit (axis the protection
coordination cable is not
connected) or servo amplifier
Base circuit
Drive unit (axis the protection
coordination cable is not
connected) or servo amplifier
Alarm
Transition No.
1) in the figure
2) in the figure
3) in the figure
5 SIGNALS AND WIRING
58
5.5 Timing chart at alarm occurrence
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
No alarm
1.5 s
ON
OFF
ON
OFF
ON
OFF
Description
If an alarm occurs on the drive unit, shut off the main circuit power supply by using an external sequence.
Turn on the main circuit power supply while the alarm on the drive unit is deactivated.
If an alarm occurs on any of the axes, input the emergency stop signal of the controller to change all axes to servo-off.
1)
No alarm
(3 s)
Alarm
Alarm occurrence
3)
No alarm
2)
(3 s)
No alarm