7.
Installation

How to Connect Wiring

7.3.1. Specifications on the Applicable Electrical Wire

Parts
Screw type
The terminals of
the unit:
・Auxiliary power
・Voltage input
・Current input
・MODBUS RTU
communication

7.3.2. Wiring of the Unit

Be sure to securely tighten the terminal screws to the terminal block.
・ Do not connect three or more electric wires to one terminal. This can cause heat
generation or a fire due to imperfect contact.
CAUTION
・ If you use a bare crimp-type terminal, you should secure a necessary insulation distance
using an insulation tube not to expose the charging part for prevention of electric shock
and short circuits.

7.3.3. Check the connection

After wiring, check the following points:
・The electric wires are securely connected.
・There is no wrong wiring.
・Used with crimp-type terminals: AWG 26 to 14
*Two-wire connection is possible.
Applicable crimp-type terminals: For M3 screw with an
outer diameter of 6.0 mm or less.
M3
Outer
diameter
Wire for use
65
Tightening
torque
0.5 N・m