4.
How to Use Test Mode
The test mode has function useful for startup of systems.
The following table shows a list of functions in the test mode.
Test menu
1.
Communication test
2. to
5. No function
6. Functions for determining
incorrect wiring
*Note: The function cannot determine all incorrect wiring. If both a voltage input and a current input are
incorrectly wired, a different pattern may be displayed.
■Test procedure
①
Press
for 2 seconds to enter the setting confirmation mode.
SET
② With
, select '9' in the setting confirmation menu number
or
+
-
③ Press
to enter the test mode.
SET
④ Execute the test in each test menu. For details, refer to 4 How to Use Test Mode.
■Test mode flow
Setting
confirmation
menu No.9
SET
+
Test menu
End
SET
+
+
(
)
Note
Operating mode
Note: The screen momentarily goes off.
For MODBUS RTU communication function, it is possible to return
fixed numerical data without measurement (voltage/current) input.
Use this for checking with the host system.
①Pattern display for incorrect wiring
When either a voltage input or current input is incorrectly wired, this
function automatically determines incorrect wiring and displays its
part on the screen. It is easier to find out the incorrect part and
useful to check the connection. *Note
②Support display for determining incorrect wiring
This function displays a current phase angle, a voltage phase
angle, and active power, voltage, and current value of each phase.
By checking each display and 9.2 A List of Examples for
Incorrect Wiring Display, it is easier to determine incorrect wiring
for measurement (voltage/current) input.
Test mode
+
Test menu 1
+
(Communication
test)
Test menu 6
+
(Functions for
determining
incorrect wiring)
Description
―
+
+
Test menu 2
(No function)
+
+
Test menu 5
(No function)
38
-
Test menu 3
(No function)
+
+
+
Test menu 4
(No function)