Connection Of Room Thermostat Of Mixers - ATTACK PELLET 30 AUTOMATIC PLUS Instructions For Use Manual

Hide thumbs Also See for PELLET 30 AUTOMATIC PLUS:
Table of Contents

Advertisement

CONNECTION OF ROOM THERMOSTAT OF MIXERS

Room thermostats affect the mixer circuit 1-4. If water is supplied to the entire heating
system of the building by a mixer, all settings of the room thermostat for the boiler must
be switched off. After disconnecting the contacts, the room thermostat reduces the
specified temperature of the mixer circuit by the value of reducing the specified
temperature of the mixer compared to the thermostat. This parameter can be found in:
Adjusting the mixer 1
The parameter value should be selected so that when the room temperature is reached
(room thermostat - disconnects contacts) the room temperature decreases. When
connecting the ecoSTER200 room panel or ecoSTER TOUCH room panel, make sure that
the parameter for selecting the thermostat is correctly selected in:
Service setting
CT6-P
Temp.
Min.
°C
Ω
-25
901,6
921,3
-20
960,6
-10
999,7
0
25
1096,9
50
1193,4
100
1384,2
125
1478,5
1572,0
150
The room thermostat of the mixer
Mixer setting 1-4
Men.
Max.
Ω
Ω
901,9
902,2
921,9
921,6
961,2
960,9
1000,3
1000,0
1097,3
1097,7
1194,0
1194,6
1385,0
1385,8
1479,4
1480,3
1574,2
1573,1
44

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pelh30plus

Table of Contents