TECHNICAL PARAMETERS

Connection voltage
Current taken by the regulator
Maximum rated current of each
operating module
Degree protection of the regulator
Ambient temperature
Storage temperature
Relative humidity
Range of temperature sensors'
measuring CT4/CT2S
Range of temperature sensors'
measuring CT6-P (outdoor sensor)
Sensors measurement accuracy CT4,
CT6-P
Terminals
Display
External dimensions
Weight of the complete device
Standards
Class of firmware
Class of protection
Degree of pollution
3
This is the current that is taken by the controller itself (when connecting 2 operating modules and a panel).
The total current consumption depends on the devices that are connected to the controller.
4
IP20 - on the front of the operating module, IP00 - on the terminal side of the operating module.
230 V~, 50 Hz
0,04 A
6 (6) A
IP20, IP00
0...50 °C
0...65 °C
5...85 % without condensation of
water vapor
0..100 °C/0..380 °C
-35..40 °C
2 °C
screw, cable cross section from 0.75
mm2 to 1.5 mm2, tightening
Network
torque 0.4 Nm, insulation length
6mm.
screw, cable cross-section up to
Signal
0.75 mm2, tightening torque 0.3
Nm, insulation length 6mm
Graphic: 128x64pix
210x115x60 mm
2 kg
PN-EN 60730-2-9
PN-EN 60730-1
A
For incorporation into class devices
I
2. degree
According to PN-EN 60730-1