Ascii Output; Binary Output - YOKOGAWA Vigilantplant mR10000 User Manual

Communication interface
Table of Contents

Advertisement

5.1 Response Syntax

ASCII Output

BINARY Output

5-2
• Example
E2 02:001
The following types of ASCII data are available. For the data formats, see section 5.2.
Setting data, basic setting data, decimal position/unit information, measured/
computed data, report data generated by the periodic printout, status information, and
user information
• Syntax
EACRLF
•••••••••••••••CRLF
:
•••••••••••••••CRLF
•••••••••••••••CRLF
ENCRLF
• Conceptual Diagram
1 byte
'E'
BINARY header
(12 bytes)
Flag
BINARY data
BINARY footer
(2 bytes)
• EB CRLF
Indicates that the data is BINARY.
• Data Length
The byte value of "flag + identifier + header sum + BINARY data + data sum."
• Header Sum
The sum value of "data length + flag + identifier."
• BINARY Data
For the output format of various data types, see section 5.3.
• Data Sum
The sum value of "BINARY data."
Note
The data length of the BINARY header section is output according to the byte order specified
with the BO command.
'B'
CR
Data length
ID
Header sum
BINARY data
Data sum