Accessing Mesa Models - Nuvation Energy NUVSSG-1250-100 Product Manual

High-voltage bms
Table of Contents

Advertisement

Model
Block
Point Name
803
Repeat
StrCellVolLoc
803
Repeat
StrMaxModTmp
803
Repeat
StrMinModTemp
803
Repeat
StrModTmpLoc
803
Repeat
StrEvt1
The term Index in the Repeating block addresses used in the above table refers to a
calculation of Index = Stack Index * Length of Repeating block. By definition, the 803
Repeating block is 16 Modbus registers in length.

7.1.5. Accessing MESA Models

MESA models are located contiguously in the Modbus address space starting at a base address of
40000. The Common Model is always located first in this space. The End Model is always last and is
used to denote the end of MESA Modbus registers. Each model located between the Common Model
and the End Model has a numeric identifier as well as a length. A handy tool that can be used to
explore the MESA Modbus registers for Nuvation Energy BMS is modpoll.exe. It is available for free
download at http://www.modbusdriver.com/modpoll.html.
Using modpoll.exe, the Common Model can be polled from a using the following command (assuming
the device has an IP address of 192.168.1.21)
Document ID: NE-PM-003
Nuvation Energy High-Voltage BMS - Product Manual
Address
Scale
Factor
40140 +Index
No
40141 +Index
Yes
40142 +Index
Yes
40143 +Index
No
40144 +Index
No
68
Purpose
Location of min/max cell voltages of a stack/string
Maximum module temperature of a stack/string
Minimum module temperature of a stack/string
Location of min/max module temperatures of a
stack/string
Alarms warnings and status bit field of a stack/string
Rev 1.2, 2021-03-03