Once the required output has been set (maximum heating), indicate
the value on the self-adhesive label supplied. For subsequent con-
trols and adjustments, refer to the set value.
9 The calibration does not entail the ignition of the boiler. By rotat-
ing the heating setpoint selector knob, the value expressed in
hundreds (e.g. 25 = 2500 rpm) is automatically displayed.
The boiler is supplied with the adjustments shown in the table. De-
pending on plant engineering requirements or regional flue gas
emission limits it is, however, possible to modify this value, referring
to the graphs below.
Start Condens 25 Kis
Curva portata termica - giri ventilatore
Thermal output curve - no. of fan rotations (MTN)
Caldaia Ciao Green 25 C.S.I.
6400
6000
5600
5200
4800
4400
4000
3600
3200
2800
2400
2000
1600
1200
4
5
6
7
8
9
10
11
12
Heat output (kW)
Start Condens 29 Kis
Curva portata termica - giri ventilatore
Thermal output curve - no. of fan rotations (MTN)
Caldaia Ciao Green 29 C.S.I.
6400
6000
5600
5200
4800
4400
4000
3600
3200
2800
2400
2000
1600
1200
4
5
6
7
8
9
10
11
12
13
Heat output (kW)
5 - Conversions from one type of gas to another
The boiler is designed to operate with methane gas (G20) according
to the rating plate. It may however be converted from one type of gas
to another by using the special kits supplied on demand.
• Methane conversion kit
• LPG conversion kit.
9 The conversion must be carried out solely by the Technical As-
sistance Service or by r personnel authorised by even when
the boiler is already installed.
9 Refer to the instructions supplied with the kit for assembly.
9 After conversion, adjust the boiler again following the indications
in the specific section and apply the new identification label con-
tained in the kit.
Conversion from a family gas to other family gas can be performed
easily also when the boiler is installed.
This operation must be carried out by professionally qualified per-
sonnel. The boiler is designed to operate with methane gas (G20)
according to the product label. It is possible to convert the boiler to
propane gas, using the special kit.
For disassembly, refer to the instructions provided below:
• Disconnect the boiler from the electricity supply and turn off the
gas tap
• Remove in the following order: air distribution box cover and casing
• Remove the fixing screw of the instrument panel
• Turn the instrument panel forward
• Remove the gas valve (A - Fig. 20)
Qm
Qn
RANGE RATED
13
14
15
16
17
18
19
20
21
22
Portata termica (kW)
Qm
Qn
RANGE RATED
14
15
16
17
18
19
20
21
22
23
24
25
Portata termica (kW)
• Remove the nozzle (B - fig. 20) and replace it with the one in the kit
• Fit the gas valve again
• Extract the silencer from the mixer
• Open the two half-shells by levering on the relative hooks
• For 25 KIS models: Replace the air diaphragm (C - Fig. 21) posi-
tioned inside the silencer
• For 29 KIS models: insert the air diaphragm (C - Fig. 21) inside
the silencer
• Reassemble the air distribution box cover
• Power-up the boiler and open the gas tap.
Adjust the boiler as described in chapter "Settings" referring to the
data concerning the LPG.
9 Conversion must be carried out by qualified personnel.
9 After the transformation, apply the new rating plate included in
the kit.

6 - Commissioning

9 The commissioning of the boiler must be carried out by qualified
personnel.
Each time the boiler is electrically powered the display shows a se-
ries of information, then the boiler begins an automatic venting cycle
that lasts about 2 minutes
The display shows the symbol
Turn the mode selector to the required position.
6.1 - Winter
23
24
25
26
Turn the function selector to within the adjustment range. The boiler
produces domestic hot water and heating water. The boiler lights
automatically in response to a heat request. The digital display indi-
cates the heating water temperature. The boiler lights automatically
in response to a request for domestic hot water. The display indi-
cates the domestic hot water temperature.
Adjustment of the heating water temperature
To adjust the heating water temperature, turn the mode selector to
within the adjustment range (turn clockwise to increase the value
and anticlockwise to reduce the value).
Depending on the type of system, the most suitable temperature
26
27
28
29
30
range can be pre-selected:
• standard systems 40-80 °C
• floor installations 20-45°C.
For details see paragraph "Boiler configuration".
heating water
domestic hot water
29
.
temperature
temperature
ENGLISH