10.5.1

Configuration

To configure for 3-network support:
10.6

Separate 4-network support

The 4 Ethernet interfaces on the XIO can support separate 4 separate networks: 2 networks by the
Enterprise Network ports (port A1 and port A2) and 2 networks by the Industrial Network ports (port B1
and port B2). Each of these ports can be configured independently of the other to provide additional
connection and topology options in the field.
IMPORTANT NOTE: Separate configuration options for these ports become available only when
the XIO 4-port switch mode is disabled.
Table 10-7
summarizes the configuration options for this scenario. In this scenario all 4 interfaces support
separate networks. Traffic in each network is isolated to that network. The XIO does not route traffic
between interfaces. This scenario supports complex applications with several XIOs and where there is
need to isolate XIOs in separate subnets or domains within in the field. Consult with ABB Technical
Support for more details.
Table 10-7: Separate 4-network support
Ports: Mode
Ethernet interface
configuration
Enterprise ports:
Two interfaces: One for
each Enterprise port
2 Networks
Industrial ports:
Two interfaces: One for
each Industrial port
2 Networks
To configure for 4-network support:
Ports
Number of
networks
A1, A2
2
B1, B2
2
XIO USER MANUAL | 2106424MNAA | 191
Number of required IP
addresses
One per port: (A1 IP, and A2 IP)
One per port: (B1 IP, B2 IP)