9.3

Use the configuration from another XIO

This procedure uses the device loader to copy a configuration saved from one device to another unit. Use
this procedure if the configuration in several devices is similar. The configuration can be shared from one
unit to another but not the calibration.
IMPORTANT NOTE: Do not use calibration data in a configuration package that was generated
from another device. Calibration data is specific to each device and links to a device's electronic
board serial number.
To send the device configuration:
NOTICE – Loss of data. After a configuration package from another unit replaces the existing
package, the device automatically uses the new startup configuration to restart (cold restart). The
previous Startup Configuration is overwritten.
To avoid loss of data and complete system reconfiguration, perform the procedures in section
Preserve data and configuration,
device.
Figure 9-20: Loader screen configuration package from another XIO
162 | XIO USER MANUAL | 2106424MNAA
to collect the data before sending a new configuration to the
9.1,