Configure Serial Communication Applications (Com Ports) - ABB XIO-08 User Manual

Extendable io
Hide thumbs Also See for XIO-08:
Table of Contents

Advertisement

The connection is successful if the Connection indicator is green. The Communication Status
under the Read Statistics section should display: No Error.
The connection failed if the Connection indicator is red. The Communication Status under the
Read Statistics section displays: Connection Timeout. Additional information on screen
parameters is available in the PCCU help topics. Click Help to display topic for the screen.
Figure 4-28: Successful RMC-XIO connection
4.7
Configure serial communication applications (COM
ports)
This section describes how to configure the XIO and its communication applications to add serial port
capacity to the RMC. Communication applications assigned to COM ports are instantiated in the XIO but
are managed (visible) from the RMC.
RMC-XIO communication takes place through the XIO Interface (client) – XIO Server connection. This
connection must be successfully established and stable as described in section
The RMC retrieves measurement data captured on the XIO COM ports and feeds it to its local
measurement applications.
IMPORTANT NOTE: A single XIO Interface instance on the RMC can manage communication with
all COM ports on an XIO. Additional XIO Interface instances are required for additional XIOs. Use a
naming convention for the XIO interface instances which allows easy identification of the associated
XIO.
Configure COM 1 - COM 8 communication ports to connect one or more peripheral serial devices. These
ports are software-configurable to support RS-232, RS-422, and RS-485.
Configure the ports with the application that supports the type of peripheral. For ABB Totalflow
peripherals, use special-purpose communication applications such as the XMV Interface.
56 | XIO USER MANUAL | 2106424MNAA