As illustrated in the following drawing, do not connect A1 and A2 or B1 and B2 to the same Ethernet
switch if they are in 1 Network Mode. Connecting both sets of ports to the same switch disables the ports.
Figure 3-5: Wrong Ethernet connection
3.4.5

Connect TFIO modules

TFIO modules connect directly to the TFIO ports on either side of the XIO. For additional information, refer
to the TFIO Module User Manual under
DANGER – Serious damage to health / risk to life. Do not connect or disconnect TFIO
modules, connectors or their terminations while energized unless the area is known to be non-
hazardous.
NOTICE – Equipment damage. When the TFIO interface is disabled, the modules remain
powered. Remove the power from the XIO before connecting or disconnecting additional TFIO
modules. Failure to power down the XIO can result in damage to the module. The procedure in this
section assumes the XIO is powered off.
Table 3-4
identifies the different module types available with the XIO that supports 12 volts to 24 volts
operation. The XIO does not support the TFIO CIM module, part number 2100421.
Table 3-4: TFIO modules
TFIO module
Valve Control Combo IO
4-20 mA Analog Output
Type II Analog Input
Combo Digital
Thermocouple Input
RTD Input
NOTICE – Equipment damage. The maximum voltage to operate legacy TFIO modules (green
modules) is 12 Vdc. More than 12 Vdc damages legacy TFIO modules. Only later versions of the
TFIO modules support voltages higher than 12 Vdc.
Additional
information.
Part number
2100412
2100415
2100418
2100543
2100869
2101018
XIO USER MANUAL | 2106424MNAA | 31
TFIO software version
2100576-007
2100715-006
2100575-006
2100563-009
2101024-001
2101027-001