Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 10
SSR6 System status register (6) control command status (client-dependent)..............69 System diagnostic values............69 Time and reason for latest protection relay reset....70 User-definable bits [Alt.2], visible on 0x,1x,3x and 4x.... 70 User-definable registers [Alt.1], visible on 3x and 4x..... 71 RET615 Point List Manual...
Page 11
LD0.SCA4GAPC2 Analog value scaling (2)......83 LD0.SCA4GAPC3 Analog value scaling (3)......83 LD0.SCA4GAPC4 Analog value scaling (4)......84 Controls.................... 84 Reset, acknowledge and trigger points........84 CTRL.CBCSWI1 Circuit breaker control (1)........ 85 CTRL.DCXSWI1 Disconnector control (1) ........85 CTRL.DCXSWI2 Disconnector control (2)........86 RET615 Point List Manual...
Page 12
LD0.LDEV1 Protection relay's warm reset (1)......86 LD0.SPCGAPC1 Generic control point (16 pcs) (1) ....87 LD0.SPCGAPC2 Generic control point (16 pcs) (2)....87 LD0.SRGAPC1 Set-reset (8 pcs) (1)...........88 LD0.SRGAPC2 Set-reset (8 pcs) (2)...........88 Unmapped control points.............89 Section 3 Glossary................. 91 RET615 Point List Manual...
The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. RET615 Point List Manual...
Cyber security deployment guideline GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V2 EN Figure 1: The intended use of documents during the product life cycle Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product version...
Content updated to correspond to the product version G/2016-05-20 5.0 FP1 Content updated H/2018-12-20 5.0 FP1 Content updated Download the latest documents from the ABB Web site http://www.abb.com/relion. 1.3.3 Related documentation Name of the document Document ID Modbus Communication Protocol Manual 1MRS756468 Symbols and conventions 1.4.1...
27 (1) PHPTUV2 3U< (2) 27 (2) Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1) PHPTOV2 3U> (2) 59 (2) Three-phase thermal overload T2PTTR1 3Ith>T/G/C (1) 49T/G/C (1) protection, two time constants Table continues on next page RET615 Point List Manual...
Page 17
I <-> O DCC (1) I <-> O DCC (1) DCXSWI2 I <-> O DCC (2) I <-> O DCC (2) Earthing switch control ESXSWI1 I <-> O ESC (1) I <-> O ESC (1) Table continues on next page RET615 Point List Manual...
Page 18
TP (3) TPGAPC4 TP (4) TP (4) Minimum pulse timer (2 pcs, second TPSGAPC1 TPS (1) TPS (1) resolution) Minimum pulse timer (2 pcs, minute TPMGAPC1 TPM (1) TPM (1) resolution) Table continues on next page RET615 Point List Manual...
Page 19
SPCGAPC2 SPC (2) SPC (2) Analog value scaling SCA4GAPC1 SCA4 (1) SCA4 (1) SCA4GAPC2 SCA4 (2) SCA4 (2) SCA4GAPC3 SCA4 (3) SCA4 (3) SCA4GAPC4 SCA4 (4) SCA4 (4) Integer value move MVI4GAPC1 MVI4 (1) MVI4 (1) RET615 Point List Manual...
The unavailable, that means, unused, data points always return value 0 when they are read. The configuration-dependent and optional data do not overlap. Supported functions 2.2.1 Supported functions in RET615 Table 2: Supported functions Function IEC 61850...
Page 22
Pulse timer (8 pcs) PTGAPC Time delay off (8 pcs) TOFGAPC Time delay on (8 pcs) TONGAPC Set-reset (8 pcs) SRGAPC Move (8 pcs) MVGAPC Generic control point (16 pcs) SPCGAPC Table continues on next page RET615 Point List Manual...
Common data 1 BitA RegA IEC 61850 name SA name Description Values CTRL.LLN0 2720 170.00 .Loc.stVal Remote/Local state 0/1=Rem/Loc 2721 170.01 .LocKeyHMI.stVal.Statio Station state 1=Station DR.RDRE1 2722 170.02 .RcdMade.stVal DR recording made 1=Made 2723 170.03 .mcd RET615 Point List Manual...
2.3.1.5 CTRL.CBXCBR1 Circuit-breaker control (1) Table 8: CTRL.CBXCBR1 Circuit-breaker control (1) BitA RegA IEC 61850 name SA name Description Values CTRL.CBXCBR1 2836 177.04 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked 2837 177.05 .mcd Table continues on next page RET615 Point List Manual...
CTRL.DCXSWI1 Disconnector control (1) Table 12: CTRL.DCXSWI1 Disconnector control (1) BitA RegA IEC 61850 name SA name Description Values CTRL.DCXSWI1 POSITION 3472 217.00 .Pos.stVal.Close Close bit 1=Close 3473 217.01 .Pos.stVal.Open Open bit 1=Open Table continues on next page RET615 Point List Manual...
In this case, it is possible to combine this LED bit interpretation with the corresponding value from the other LED state interpretation. LEDx Signal 1 Signal 2 ALARM RESET GUID-051741E8-4D66-412C-BA0A-0B849B5E58F2 V1 EN Figure 3: Separate signals wired to OK and ALARM inputs RET615 Point List Manual...
ALARM is red and green for OK. Colors can, however, be reconfigured with a setting parameter. LEDx Signal ALARM RESET LEDx Signal ALARM RESET GUID-775477F8-C2DE-4138-B2C0-6B7C2774D4D2 V1 EN Figure 4: Signal wired to either OK or Alarm input RET615 Point List Manual...
LD0.PHPTUV1 Three-phase undervoltage protection (1) BitA RegA IEC 61850 name SA name Description Values LD0.PHPTUV1 3138 196.02 .Str.general START General start 1=Start 3139 196.03 .mcd 3140 196.04 .Str.phsA Phs A start 1=Start Table continues on next page RET615 Point List Manual...
LD0.T2PTTR1 Three-phase thermal overload protection, two time constants (1) BitA RegA IEC 61850 name SA name Description Values LD0.T2PTTR1 2972 185.12 .Str.general START General start 1=Start 2973 185.13 .mcd 2974 185.14 .AlmThm.general ALARM Thermal alarm 1=Alarm Table continues on next page RET615 Point List Manual...
X110-Input 1 State 0/1=Off/On 3217 201.01 .mcd .mom-only Mom only alternative 3218 201.02 .Ind2.stVal X110-Input 2 State 0/1=Off/On 3219 201.03 .mcd .mom-only Mom only alternative 3220 201.04 .Ind3.stVal X110-Input 3 State 0/1=Off/On Table continues on next page RET615 Point List Manual...
X100-Output 1 State 0/1=Off/On 3249 203.01 .mcd .mom-only Mom only alternative 3250 203.02 .SPCSO2.stVal X100-Output 2 State 0/1=Off/On 3251 203.03 .mcd .mom-only Mom only alternative 3252 203.04 .SPCSO3.stVal X100-Output 3 State 0/1=Off/On Table continues on next page RET615 Point List Manual...
X110-Input 6 State 0/1=Off/On 3227 201.11 .mcd .mom-only Mom only alternative 3228 201.12 .Ind7.stVal X110-Input 7 State 0/1=Off/On 3229 201.13 .mcd .mom-only Mom only alternative 3230 201.14 .Ind8.stVal X110-Input 8 State 0/1=Off/On Table continues on next page RET615 Point List Manual...
X130-Input 5 State 0/1=Off/On 3193 199.09 .mcd .mom-only Mom only alternative 3194 199.10 .Ind6.stVal X130-Input 6 State 0/1=Off/On 3195 199.11 .mcd .mom-only Mom only alternative 3264 204.00 .SPCSO1.stVal X130-Output 1 State 0/1=Off/On Table continues on next page RET615 Point List Manual...
All premapped three-phase protection function stages, operate/phase-dependent objects added BitA RegA IEC 61850 name SA name Description Values LD0.xxxxxxxx (various) .Op.phsA Phs A operate 1 = Operate .mcd .Op.phsB Phs B operate 1 = Operate .mcd .Op.phsC Phs C operate 1 = Operate .mcd RET615 Point List Manual...
0/1=Off/On .mcd .SPCSO4.stVal Ouput state 4 0/1=Off/On .mcd .SPCSO5.stVal Ouput state 5 0/1=Off/On .mcd .SPCSO6.stVal Ouput state 6 0/1=Off/On .mcd .SPCSO7.stVal Ouput state 7 0/1=Off/On .mcd .SPCSO8.stVal Ouput state 8 0/1=Off/On Table continues on next page RET615 Point List Manual...
Short description of the signal. See the technical manual for more information. Also, if a register is writable, it is stated here. Values The value range of the original IEC 61850 value, that is, before scaling. RET615 Point List Manual...
IEC 61850 name SA name Description Values 8011 Execute register 8012 Password reg 1 acc to setting 8013 Password reg 2 acc to setting 8014 Control register < single bit > 8015 Confirm register < single bit > RET615 Point List Manual...
IEC 61850 name SA name Description Values 8031 Execute register 8032 Password reg 1 acc to setting 8033 Password reg 2 acc to setting 8034 Control register < single bit > 8035 Confirm register < single bit > RET615 Point List Manual...
Day/Hour 9256 - Minute, Second Min/Sec 9257 - Millisecond Millisecond 9258 Event identification 9259 Data object ID1 9260 Data object ID2 9261 Event data value 1 9262 Event data value 2 Table continues on next page RET615 Point List Manual...
Page 64
- Unread records left 0...499 Timestamp of record 9287 - Year, Month Year/Month 9288 - Day, Hour Day/Hour 9289 - Minute, Second Min/Sec 9290 - Millisecond Millisecond 9291 Event identification 9292 Data object ID1 Table continues on next page RET615 Point List Manual...
Page 65
Record 7 data to read: If selected 9318 - Record sequence num 1...9999 9319 - Unread records left 0...499 Timestamp of record 9320 - Year, Month Year/Month 9321 - Day, Hour Day/Hour Table continues on next page RET615 Point List Manual...
Page 66
- Millisecond Millisecond 9346 Event identification 9347 Data object ID1 9348 Data object ID2 9349 Event data value 1 9350 Event data value 2 Record 10 data to read: If selected Table continues on next page RET615 Point List Manual...
9408 Timestamp quality 2.4.1.13 Fault record data The table shows all potential data available in the fault record application. Which data is actually recorded depends on the functions available and enabled in the protection relay's configuration. RET615 Point List Manual...
Page 68
0 [pu] 9431 1000 .RstAPhsA.mag Bias current phs A 0.000… 50.000 [pu] 9432 1000 .RstAPhsB.mag Bias current phs B 0.000… 50.000 [pu] 9433 1000 .RstAPhsC.mag Bias current phs C 0.000… 50.000 [pu] Table continues on next page RET615 Point List Manual...
Page 69
.VZro1.mag Voltage Zro-Seq(1) 0.000...4.000 [×Un] 9455 1000 .VPsSeq1.mag Voltage Ps-Seq(1) 0.000...4.000 [×Un] 9456 1000 .VNgSeq1.mag Voltage Ng-Seq(1) 0.000...4.000 [×Un] 9457 .MaxTmpRl.mag PTTR thermal level 0.00...99.99 9458 .AMaxNgPs.mag PDNSPTOC1 ratio I2/I1 0.00...999.99 Table continues on next page RET615 Point List Manual...
Page 70
Voltage phs CA(2) 0.000...4.000 [×Un] 9480 1000 .VRes2.mag Voltage Uo(2) 0.000...4.000 [×Un] 9481 1000 .VZro2.mag Voltage Zro-Seq(2) 0.000...4.000 [×Un] 9482 1000 .VPsSeq2.mag Voltage Ps-Seq(2) 0.000...4.000 [×Un] 9483 1000 .VNgSeq2.mag Voltage Ng-Seq(2) 0.000...4.000 [×Un] Table continues on next page RET615 Point List Manual...
Protection relay's real-time clock (in UTC time mode) - read and write (synchronize) RegA Type Scale IEC 61850 name SA name Description Values 9211 Control register 0...2 9212 Year 2000...2999 9213 Month 1...12 9214 1...31 9215 Hour 0...23 Table continues on next page RET615 Point List Manual...
Data category 16 has changed 1=Changed 2.4.1.21 SSR5 System status register (5) device alive register Table 124: SSR5 System status register (5) device alive register RegA Type Scale IEC 61850 name SA name Description Values Device alive counter 0...65535 RET615 Point List Manual...
Last internal fault code DR.RDRE1 2062 .FltNum.stVal Num. of DR recordings 0...N 2063 .MemUsed.stVal DR memory used 0...100 [%] LD0.LPHD1 2064 .NumPwrUp.stVal Num. of cold starts 0...65535 2065 .WrmStr.stVal Num. of warm starts 0...65535 Table continues on next page RET615 Point List Manual...
Values LD0.CAVMMXU1 Demand value 2001 1000 .A.phsA.cVal.mag I_DMD_A Phs A amplitude 0.00…50.0 [xIn] 2002 1000 .A.phsB.cVal.mag I_DMD_B Phs B amplitude 0.00…50.0 [xIn] 2003 1000 .A.phsB.cVal.mag I_DMD_C Phs C amplitude 0.00…50.0 [xIn] Table continues on next page RET615 Point List Manual...
Page 78
Time quality LD0.CMIMMXU1 Min demand values 1000 .A.phsA.cVal.mag Max demand IL1 Phs A amplitude 0.00…50.0 [xIn] 1000 .A.phsB.cVal.mag Max demand IL2 Phs B amplitude 0.00…50.0 [xIn] 1000 .A.phsC.cVal.mag Max demand IL3 Phs C amplitude 0.00…50.0 [xIn] RET615 Point List Manual...
Minute - second 2039 Milliseconds 2040 Time quality 0.00...40.0 2041 1000 .MaxAmpsB.mag Max demand IL2 Max. phs B demand [xIn] Update time stamp See doc. 2042 Year - month 2043 Day - hour Table continues on next page RET615 Point List Manual...
LD0.CSMSQI1 Sequence current measurement (1) RegA Type Scale IEC 61850 name SA name Description Values LD0.CSMSQI1 Sequence of currents 0.00...40.0 1000 .SeqA.c1.instCVal.mag I1_INST Positive amplitude [xIn] 0.00...40.0 1000 .SeqA.c2.instCVal.mag I2_INST Negative amplitude [xIn] 0.00...40.0 1000 .SeqA.c2.instCVal.mag I3_INST Zero amplitude [xIn] RET615 Point List Manual...
-/+ 999,999 .TotVAr.mag Reactive power Q -/+ 999,999 .TotVA.mag Apparent power S -/+ 999,999 LD0.PEMIMMXU1 Min demand value .TotW.mag Active power P -/+ 999,999 .TotVAr.mag Reactive power Q -/+ 999,999 .TotVA.mag Apparent power S -/+ 999,999 RET615 Point List Manual...
Max demand Io Residual amplitude 0.00…50.0 [xIn] 1996 Year - month 1997 Day - hour 1998 Minute - second 1999 Milliseconds 2000 Time quality LD0.RCMIMMXU1 Min. demand value 1000 .A.res.cVal.mag Min demand Io Residual amplitude 0.00…50.0 [xIn] RET615 Point List Manual...
1) See the technical manual. 2.4.1.40 LD0.RESCMMXU2 Residual current measurement (2) Table 143: LD0.RESCMMXU2 Residual current measurement (2) RegA Type Scale IEC 61850 name SA name Description Values LD0.RESCMMXU2 Residual current (2) 0.00...40.0 1000 .A.res.instCVal.mag I0_INST Amplitude [xIn] RET615 Point List Manual...
LD0.SSCBR1 2070 .InaTmdCnt.stVal INA_DAYS CB inactive days 0..65535 2071 .TmmsOpn.mag T_TRV_OP Open travel time 0..60000 [ms] 2072 .TmmsCls.mag T_TRV_CL Close travel time 0..60000 [ms] 0.00…99.99 2073 .TmsSprCha.mag T_SPR_CHR Spring charge time Table continues on next page RET615 Point List Manual...
Unmapped registers are register data that have no initial Modbus mapping locations, but can be added to the user-definable Modbus area using the Communication Management tool in PCM600. The initial register type settings of these objects have RET615 Point List Manual...
LD0.MVI4GAPC1 Integer value move (1) Table 159: LD0.MVI4GAPC1 Integer value move (1) RegA Type Scale IEC 61850 name SA name Description Values LD0.MVI4GAPC1 .ISCS01.stVal OUT1 - Integer value 1 (high) +2147483647 - Low word Table continues on next page RET615 Point List Manual...
1000 .AnValOut1.mag AO1_VALUE Analog value 1 after scaling 0…N 1000 .AnValOut2.mag AO2_VALUE Analog value 2 after scaling 0…N 1000 .AnValOut3.mag AO3_VALUE Analog value 3 after scaling 0…N 1000 .AnValOut4.mag AO4_VALUE Analog value 4 after scaling 0…N RET615 Point List Manual...
Table 167: CTRL.DCXSWI1 Disconnector control (1) IEC 61850 name SA name Description Values CTRL.DCCSWI1 2144 7.00 .Pos.Oper.ctlVal Select open 1=Select 2145 7.01 .Pos.Oper.ctlVal Select close 1=Select 2146 7.02 .Pos.Oper.ctlVal Cancel selection 1=Cancel Table continues on next page RET615 Point List Manual...
.Pos.Oper.ctlVal Direct close 1=Close 2.5.6 LD0.LDEV1 Protection relay's warm reset (1) Table 170: LD0.LDEV1 Protection relay's warm reset (1) IEC 61850 name SA name Description Values LD0.LDEV1 2080 3.00 .WrmStrCmd.Oper.ctlVal Warm reboot of protection relay 1=Reboot RET615 Point List Manual...
Output 1 control 0/1=Off/On 2129 6.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On 2130 6.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On 2131 6.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On 2132 6.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On Table continues on next page RET615 Point List Manual...
Modbus data mappings 2.5.11 Unmapped control points Table 175: Unmapped control points IEC 61850 name Description Value LD0.LLN0.MeasStatRs.Oper.ctlVal Reset all min. and max. demands 1=Reset LD0.LLN0.PQRs.Oper.ctlVal Reset all power quality data 1=Reset LD0.FLTRFRC1.RcdRs.Oper.ctlVal Reset fault record data 1=Reset RET615 Point List Manual...
Intelligent electronic device Light-emitting diode LHMI Local human-machine interface Modbus A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. PCM600 Protection and Control IED Manager RET615 Point List Manual...