any serial communication setup, parameters on the XIO must match the parameters of the RMC
application that is processing the data received from the XIO COM port.
If you are experiencing issues communicating when using the Ethernet-serial passthrough function, verify
the configuration on the XIO first and then troubleshoot serial communication. The following figure shows
an RMC XMV application configured for communication with an XIO which is unable to receive XMV data.
Figure 6-14: RMC failure to receive data – XMV Interface does not have XMV values
The procedures in this section assume that the serial device is properly wired to the XIO COM port. If
none of the procedures included in this section resolves communication failure, be sure to check the
wiring again.
6.3.1

Missing or mismatched TCP port

A mismatched or missing TCP port on either the RMC or XIO prevents communication.
Figure 6-15
shows
the example of an RMC XMV application (left) using Ethernet-Serial Passthrough to communicate to a port
on an XIO (right). Note that the RMC has a destination IP and TCP port, but the TCP port in the XIO is
missing. The RMC will be unable establish a connection until the XIO has a matching and valid TCP port.
106 | XIO USER MANUAL | 2106424MNAA