System Configuration And Set-Up - Ametek 90B Series Installation And Configuration Manual

Annunciator system
Table of Contents

Advertisement

S
C
YSTEM
ONFIGURATION AND
The SERIES 90B Annunciator is already factory configured per the model
number. Most of the configuration of the system is made using software,
however some settings such as relay contact arrangement (Form A or Form B)
needs to be configured by the user. The default configurations are specified
below:
Item
Inputs
N.O. (normally open), N.C. (normally
closed) Field Contact Inputs
Field Contact Voltage
(12, 24, 48, 125VDC, 120VAC)
OR
(24-125VDC)
Common FCV (field contact voltage)
or Isolated FCV
Input Module Address Setting
Operational Sequence (A, M, etc)
Sequence Grouping
Input Response
Critical/Non-Critical Assignment
Optional
Form A (normally open), Form B
Repeat Relays
Contacts (normally closed)
Form C Contacts (SPDT)
Energized or De-Energized Relays
Repeat Relay Operation
CSM Functions Auxiliary Contact Output Type
(Form A, Form B)
Auxiliary Contact Output Mode
(Energized or De-Energized)
Auxiliary Contact Output Operation
(Horn, Reflash, Fault, Watchdog,
Power Monitor, Ground Fault)
Other system-wide functions
Serial
RS-232 , RS-485
Communication
RS-485 Termination Jumper
Module
Flash Synchronization (master/slave)
* NO/NC Field Inputs can be configured via the software or hardware, but
not both. Choose one method only.
Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
S
-U
ET
P
Default
Setting
N.O.
Factory
Configured
Per Model
Number
1 group
50 msec
Non-Critical
Form A
Factory
Configured
Per Model
Number
De-Energized Software
Follows Input
Form A
De-Energized Software
Critical Horn
& Non-Critical
Horn
None
Selected
RS-232
Out
Master
i.
Configuration
Method
Software or
Hardware *
Hardware
Hardware
Hardware
Software
Software
Software
Software
Hardware
Hardware
Software
Hardware
Software
Software
Software
Software
Hardware
7