Controls; System Relays; Audible Devices - Ametek 90B Series Installation And Configuration Manual

Annunciator system
Table of Contents

Advertisement

Controls

Pushbuttons
Integral Pushbutton Option (INTB, LPPB):
Reset
(4) External Pushbutton Inputs:
5VDC @0.002 mA per Pushbutton
(provided by Annunciator)
Switch Input (Option SW)
Software configurable for:
Inhibit of LED Lamps, Horn, Repeat Relay Outputs or CSM Common Relay
Outputs
5VDC @0.002 mA (provided by Annunciator)

System Relays

Alarm Grouping
Critical or Non-Critical Alarms:
Used to provide separate horns, or other relay outputs
Critical Alarms have priority over Non-Critical (can be disabled)
Standard Relays
(2) Relays Software Configurable for:
Critical or Non-Critical Horn, Ringback Horn
Energized or De-Energized Relay Coil, selectable in Software
Form A or Form B (N.O. or N.C.) Contact, Selectable by Jumper
Optional Relays (Option RLY)
(2) Additional Relays Software Configurable for:
Critical or Non-Critical Horn, Ringback Horn, Critical or Non-Critical Reflash,
Critical or Non-Critical Fault, Power Fail, System Watchdog, or Ground Fault
Detect)
Energized or De-Energized Relay Coil, selectable in Software
Form A or Form B (N.O. or N.C.) Contact, Selectable by Jumper
Relay Ratings:
24VDC @ 3.0 Amps
110VDC @ 0.1 Amps
120VAC @ 3.0 Amps
Resistive Load

Audible Devices

Internal 80db @ 30cm audible device (option HN)
External Audible Devices available
94
Test, Acknowledge, Silence and
Test, Acknowledge, Silence and Reset
Selectable in software per input
Series 90B ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL