CLMD12 User's Manual
3.5.1.6.6 ECB Model
This read-only field shows the revision level of the ECB (electronic circuit breaker).
3.5.1.6.7 Trip Delay
This parameter allows you to configure the trip delay for the breaker (the current through the
breaker must exceed the current rating of the breaker for this amount of time for the breaker to
trip). This can be set in the range of 0 ms to 750 ms.
3.5.1.6.8 Inrush Delay
This parameter allows you to configure the inrush delay for the breaker. When the breaker is
switched from OFF to ON, the current through the breaker can exceed the current rating of the
breaker for this amount of time without the breaker tripping. This allows for a brief period of
current inrush, preventing the circuit from inadvertently tripping when energized. This can be
set in the range of 0 ms to 1500 ms.
3.5.1.6.9 Default Dim Value
This parameter allows you to configure the percent dimming value for the breaker when the
CLMD12 is powered on. This value will be applied only if the Dimming Allowed box is checked.
This can be set in the range of 5% to 100% with a resolution of1%.
3.5.1.6.10
Current Dim Value
This read-only field shows the percent dimming value for the breaker.
3.5.1.6.11
Dimming Allowed
This parameter allows you to configure whether the channel is dimmable. Check this box to
allow dimming commands to change the dimming level of the breaker and clear this box to
force the breaker to operate at 100% dimming level.
3.5.1.6.12
Combine With
To parallel two breakers, select the number of the breaker you wish to combine this breaker
with. The dropdown box will present a list of other breakers with the same current capability
which may be paralleled with this breaker, If two breakers are paralleled, the breaker with the
higher number mirrors the state of the breaker with the lower number. For example, if you
parallel Breaker 1 and Breaker 2, any change in state of Breaker 1 will be mirrored by Breaker
2.
3.5.1.6.13
Factory Current Rating
This parameter allows you to configure the maximum value to which the Current Rating can
configured. This parameter should be configured to the current rating for the wire connected to
this breaker. The value you can program into this field is limited by the current capacity of the
channel being programmed.
3.5.1.6.14
Current Rating
This parameter allows you to configure the desired trip level for this breaker. Exceeding this
current will initiate a trip. The value you program into this field will be limited by the value in the
Factory Current Rating field.
3.5.1.6.15
Current
This read-only field shows the real-time current passing through the breaker.