WARNING
The System Ground signal (Connector J2, Pin 6) must be connected to the
supply voltage ground reference for proper system operation, regardless of
whether any of the Discrete Input signals are connected.

3.4.4 DC Power Connection

Connect a source of DC power with a ring terminal to the 1/4"-20 stud on the top of the device,
being careful not to torque the connection beyond the specified value of 20 in-lbs. (2.26 N·m).
Ensure that the cable providing the DC power is protected by a fuse or circuit breaker with a
value appropriate to protecting the wire or the 75A maximum specification of the CLMD12,
whichever is less.

3.4.5 Checking Connections

Once all of the connections to the CLMD12 have been completed, check to see that
information is being properly transmitted by observing an appropriate NMEA 2000
you don't see channel on/off status, refer to Section 6, "Troubleshooting".

3.5 Configuring the CLMD12

The CLMD12 will transmit data over the NMEA 2000
however, it may require configuration, depending on the type of switches monitored and the
number of similar products on the NMEA 2000
within the CLMD12, which are detailed in the remainder of this section.
You configure the CLMD12 using Maretron N2KAnalyzer
following subsections describe the configurable parameters in the CLMD12.

3.5.1 General Tab

This tab contains commonly-used configuration items.
Revision 1.6
®
network as it is shipped from the factory;
®
network. There are several configurable items
®
or Carling G2Analyzer software. The
®
display. If
Page 11

Advertisement

Table of Contents
loading

This manual is also suitable for:

M-power clmd12

Table of Contents