baltur GI Series Instruction page 32

Hide thumbs Also See for GI Series:
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 19
AIR / GAS PRINCIPLE DIAGRAM
1
Air regulation servomotor
2
Air pressure switch
3
Maximum gas pressure switch
4
Gas supply modulating throttle valve
5
Main flame gas valve
6
Valve seal control device (integral with the control box) with pressure gauge
7
Safety gas valve
E
8
Minimum gas pressure switch
9
Gas pressure regulator
N
10 Gas filter
11 Anti-vibration coupling (not included)
G
12 Ball valve (not included)
13 Gas regulation servomotor
L
I
S
MEASUREMENT OF THE IONISATION CURRENT
H
The minimum ionisation current for the control box to run is 1.4 µA.
The burner flame generates a markedly higher current that will not
normally require any control box checks.
If you want to measure the ionisation current you have to connect
a milliammeter in series to the ionisation electrode cable, as shown
in diagram.
14 / 16
0006081361_200805
N° 0002910900
REV.:08/11/2004