UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Table 11-7 Battery electrical specifications
Item
Battery voltage (VRLA
battery)
Battery cold start
Charger output power
Battery string sharing
Charging voltage
(VRLA battery)
Battery type
The UPS supports the SmartLi. For details about the parameters, see the
User Manual .
Issue 03 (2021-04-22)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Specifications
360–600 V DC
● 12 V batteries (30–50 batteries optional, 0 by
default)
– 40–50 batteries: not derated
– 38–39 batteries: derated to 0.9
– 34–37 batteries: derated to 0.8
– 30–33 batteries: derated to 0.7
● 2 V batteries (180–300 batteries optional, 0 by
default)
– 240–300 batteries: not derated
– 228–239 batteries: derated to 0.9
– 204–227: derated to 0.8
– 180–203: derated to 0.7
NOTE
The number of batteries is 0 by default and needs to be set
based on site requirements. Batteries have no neutral wire,
and an odd number of batteries are supported.
If a mains outage occurs, batteries can start the UPS to
supply power to loads.
Under rated conditions, the maximum charge power is
15% of module power, and the charge current is
limited to 30 A.
Lead-acid battery: Battery string sharing is supported
in a parallel system. No battery is shared by default.
SmartLi 2.0: Battery string sharing is supported. When
multiple UPSs are connected in parallel, the lithium
battery cabinet can be expanded for half a cabinet. No
battery is shared by default.
● Default equalized charging voltage: 2.35 V/cell
● Default float charging voltage: 2.25 V/cell
● VRLA
● SmartLi
11 Technical Specifications
SmartLi
208