UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Item
Inverter output
short-circuit
capability
Bypass overload
capability
Table 11-9 System electrical specifications
Item
Parallel system
reliability
Issue 03 (2021-04-22)
1200 kVA
● Load > 150%: transfers to
bypass mode after 200 ms
or more; withstands at
least 50 shocks
If the initial load rate is less than 40%, the inverter output
short-circuit can tolerate twice the rated current for 300 ms.
● 30°C: runs continuously at
135% load; generates
only alarms and depends
on overtemperature
protection at 135–150%
load
● 40°C: runs continuously at
125% load; generates
only alarms and depends
on overtemperature
protection at 125–150%
load
● At 40°C, if the load of the
bypass single-phase or
three-phase is 150%–
200%, the bypass will be
shut down in 5 minutes,
and the hardware
depends on
overtemperature
protection. If the load of
the bypass single-phase
or three-phase is greater
than 200%, the bypass
will be shut down in 1
minute, and the hardware
depends on
overtemperature
protection.
● Load > 1000%: runs for
100 ms
Specifications
Redundant parallel signals
Copyright © Huawei Technologies Co., Ltd.
11 Technical Specifications
1600 kVA
● 30°C: runs continuously
at 110% load; runs for 10
min and then depends on
overtemperature
protection at 110%–
125% load
● 40°C: runs continuously
at 100% load; generates
only alarms and depends
on overtemperature
protection at 100–125%
load
● 40°C: generates only
alarms and depends on
overtemperature
protection at 125%–
1000% load
● Load > 1000%: runs for
100 ms
211