UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Table 6-6 Power cable terminal requirements
Port
Description
Mains input/
bypass input/
output/PE
Step 6 Install the connector boxes.
Step 7 Install a signal cable.
Figure 6-31 Installing signal cables between the UPS and the SmartLi
(1) Monitoring interface unit in the master SmartLi cabinet
----End
Issue 03 (2021-04-22)
Connection
Method
Crimped DT
terminals
If you need to log in to the WebUI of the UPS monitoring system, connect the
network port on a PC to the FE port on the monitoring interface card.
If the UPS needs to connect to an external network management device,
connect the external network management device to the RS485 port on the
monitoring interface card.
If the UPS needs to connect to the SmartLi, connect the COM port on the
monitoring interface unit in the master SmartLi cabinet to the COM2 port on
the monitoring interface card.
NO TE
The figure uses the cable connection between the UPS and the SmartLi as an example.
Copyright © Huawei Technologies Co., Ltd.
Bolt
Bolt
Specifications
Length
M12
45 mm
6 Installation
Torque
47 N·m
84