Figure 6-17 Battery copper bar wiring holes (1600 kVA, unit: mm)
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
Table 6-2 Recommended power cable cross-sectional areas (900–1200 kVA)
Item
Mains input
Mains input
current (A)
Recomme
nded
cross-
sectional
area
(mm
Bypass input
Bypass input
current (A)
Recomme
nded
cross-
sectional
area
(mm
Issue 03 (2021-04-22)
NO TE
● The rated voltage of the SmartLi is 512 V. The voltage is 408 V at the maximum
discharge current.
● If the top cabling component and bottom cabling cabinet are configured, refer to the
recommended cable specifications in the following table for the mains input, bypass
input, and output.
900 kVA
1672
L1
5 x 240
L2
5 x 240
L3
5 x 240
2
N
5 x 240
)
PE
2 x 240
1367
L1
5 x 240
L2
5 x 240
L3
5 x 240
2
)
N
5 x 240
Copyright © Huawei Technologies Co., Ltd.
1000 kVA
1100 kVA
1858
2044
5 x 240
6 x 240
5 x 240
6 x 240
5 x 240
6 x 240
5 x 240
6 x 240
2 x 240
2 x 240
1519
1671
5 x 240
6 x 240
5 x 240
6 x 240
5 x 240
6 x 240
5 x 240
6 x 240
6 Installation
1200 kVA
2229
6 x 240
6 x 240
6 x 240
6 x 240
2 x 240
1823
6 x 240
6 x 240
6 x 240
6 x 240
71