Alarms Config - RACOM RAy3 User Manual

Microwave link
Hide thumbs Also See for RAy3:
Table of Contents

Advertisement

Configuration
The comment field can be used to add user defined comments when an 'alarm acknowledge' is
performed. Use this comment field to describe important details of the alarm status. The comment
can be up to 50 characters long. Special characters are not allowed.
The alarm can be acknowledged multiple times with different comments. Every acknowledgement
is written to the internal memory and is visible in the alarm log.

5.4.4.3. Alarms Config

Fig. 5.17: Menu Link settings / Alarms / Config
The diagnostics system of the link monitors the operation of both units.
It generates various event outputs - system warnings and alarms. The event is always written to the
system log and indicated in the status bar and Alarms/Status screen. Some events have adjustable
thresholds. Events with no adjustable thresholds may or may not be Enabled. If they are not Enabled,
the system event is not activated even if the system status is changed.
If the event goes above or below the set parameter limits or a link goes down or up, you can choose
to send an SNMP trap. All SNMP traps are OFF in defaults.
Alarms
• Inside temperature [°C]
Default >80
Temperature inside the unit (on the modem board). Active if temperature exceeds the threshold.
• Voltage min [V]
Default <40
Lower threshold of supply voltage. Active if voltage drops below min voltage threshold.
The same SNMP trap (same OID) applies for both Voltage min and max.
• Voltage max [V]
102
RAy3 Microwave Link – © RACOM s.r.o.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ray3-17Ray3-24

Table of Contents